Note: Additional parameters for defrost (if using an external SSR/relay) and digital inputs exist but are rare on the base SB655 C model. The Eliwell SB655 C manual lists several alarm codes on the display. Here is how to interpret them:
A: The most common default is 3 (three). If that fails, try 5 , 55 , 22 , or 0 . If none work, the password has been changed by a previous technician. You may need to contact technical support for a backdoor reset code.
This article serves as a complete digital handbook. We will cover everything from the technical specifications and terminal functions to step-by-step programming, parameter lists, alarm codes, and common wiring diagrams. The Eliwell SB655 C is a microprocessor-based digital temperature controller with an onboard relay output. It is part of Eliwell’s “Easy” series, known for its simplicity and robustness. The device is typically panel-mounted and features a bright 3-digit LED display, four buttons for navigation, and a user-friendly interface. eliwell sb655 c manual
| Alarm Code | Meaning | Likely Cause & Solution | | :--- | :--- | :--- | | | Internal EEPROM error | Faulty controller; replace unit. | | E1 | Probe 1 faulty (open circuit) | Broken probe, loose wire at terminals 2/3, or wrong S1P setting. | | E2 | Probe 1 short circuit | Moisture in probe tip, damaged probe, or short across terminals 2-3. | | HA | High temperature alarm | Temperature above ALU (alarm upper limit). Check compressor, refrigerant, fans. | | LA | Low temperature alarm | Temperature below ALL (alarm lower limit). Check setpoint, probe placement. | | PFA | Probe failure alarm – output forced | Controller is running a timed cycle because E1/E2 is active. Check probe wiring. |
A: That is not an error. The display is showing that the compressor is in a minimum off-time delay (parameter dLy). It is protecting the compressor from short cycling. The countdown value will appear (e.g., “3” for 3 minutes remaining). Note: Additional parameters for defrost (if using an
| Terminal | Label | Function | Typical Connection | | :--- | :--- | :--- | :--- | | 1 | 12V | +12 Vdc output for probe (power supply) | Connect to probe + | | 2 | GND | Ground reference for probe | Connect to probe - | | 3 | PTC/NTC | Analog input for temperature probe (Probe 1) | Signal wire (typically white or yellow) | | 4 | N | Neutral (Power supply input) | 230V Neutral Line | | 5 | L | Live (Power supply input) | 230V Live Line | | 6 | NO | Normally Open output relay contact | Compressor contactor coil (L1) | | 7 | COM | Common output relay contact | Compressor contactor common | | 8 | NC | Normally Closed (rarely used) | Alarm circuit or unused |
If you are searching for the Eliwell SB655 C manual , you likely have a refrigeration or HVAC control panel in front of you that needs programming, troubleshooting, or an electrical connection check. The Eliwell SB655 C is a classic, highly reliable digital temperature controller widely used in commercial refrigeration, cold rooms, industrial freezers, and HVAC systems. However, without the manual, navigating its parameters and terminal blocks can be daunting. If that fails, try 5 , 55 , 22 , or 0
A: ELIWELL NTC 10kΩ at 25°C (probe type: NTC103AT) is standard. PTC probes (PtC) are also supported if you change parameter S1P to “PtC.” Do not use PT100 (RTD) probes; they are incompatible. 10. Conclusion The Eliwell SB655 C is a workhorse of the refrigeration industry. Whether you are building a new cold room or repairing a frozen display case, understanding its manual is key to a long, trouble-free service life.